Tag Archives: delta plc programming training

How to program Delta’s plc programming time relay

Delta plc programming time relay programming method

The Delta PLC timer is a time unit of 1ms, 10ms, 100ms. The timing mode is counted. When the current value of the timer = set value, the output coil is turned on. The set value is the decimal K value. The available data register D is used as the set value.

The actual set time of the timer = the time unit * set value.

Programming can be distinguished according to its nature:

1. General timer:

Generally, the timer is used to count once when the END instruction is running. When the TMR instruction is running, if the timing is reached, the output coil is turned on.

The ladder diagram of the programming looks at the following figure:

Programming Examples:

When X0=On, the current value of the timer T0 is counted at 100ms, and when the timer current value = set value K100, the output coil T0=On.

When X0=Off or power failure, the current value of timer T0 is cleared to 0, and output coil T0 becomes Off.

2. Integrated timer

The integrated timer counts once when the END instruction is running. When the TMR instruction is running, if the timing arrives, the output coil is turned on.

The ladder diagram of the programming looks at the following figure:

Programming Examples:

When X0=On, the current value of the timer T250 is counted at 100ms, and when the current value of the timer = set value K100, the output coil T0=On.

When X0=Off or power failure during timing, the timer T250 pauses and the current value remains unchanged. When X0 is on again, it continues to count, and its current value is accumulated up until the current value of the timer = set value K100. Coil T0 = On.

How to specify the set value: Actual set time of the timer = Time unit * Set value.

1. Constant specification K: The set value directly specifies the decimal constant K value.

2. Indirect designation D: Set value Use data register D for indirect designation.

What module is dvp16sp11r?

DVP16SP11R

 is the Delta plc module. 8-channel input, 8-channel relay output hybrid IO expansion module.

dvp16sp11r

dvp16sp11r  manual

Model
Item
DVP14SS211R
DVP14SS211T
DVP12SS211S
Power supply voltage
24 VDC (-15 to 20%)
(with counter-connection on the polarity of DC input power)
DVPPS01/PS02: input 100 to 240 VAC, output 24 VDC/1A (PS02: 2A)
Inrush current
Max. 7.5 A@24 VDC
Fuse capacity
1.85 A/30 VDC, Polyswitch
Power consumption
1.8W
1.5W
Power
With counter-connection on the polarity of DC input power
Insulation resistance
> 5 M Ω (all I/O point-to-ground: 500 VDC)
Noise immunity
ESD (IEC 61131-2, IEC 61000-4-2): 8kV Air Discharge
EFT (IEC 61131-2, IEC 61000-4-4): Power Line: 2kV, Digital I/O: 1kV,
Analog & Communication I/O: 1kV
RS (IEC 61131-2, IEC 61000-4-3): 26MHz ~ 1GHz, 10V/m
Grounding
The diameter of grounding wire cannot be smaller than the wire diameter of terminals L and N (All DVP units should be grounded directly to the ground pole).
Operation / storage
Operation: 0 to 55°C (temp.), 50 to 95% (humidity), Pollution degree 2
Storage: -25 to 70°C (temp.), 5 to 95% (humidity)
Vibration / shock resistance
International standards: IEC61131-2, IEC 68-2-6 (TEST
Fc)/IEC61131-2 & IEC 68-2-27 (TEST Ea)
Weight (g)
97
82.5
90