MITSUBISHI PLC’s timer to the time contact action Is it immediately reset or maintained

In MITSUBISHI PLC, timers can be divided into retention type and non maintenance type (taking FX series as an example). If T0–T199 is not maintained, T200–T250 is maintained.
For your problem, it should be answered: if you use any of the T0–T199 in the program, the contact will act when the timer goes to the time. As long as the condition of the timer coil is true, the contact is kept, and the contact will be reset immediately as long as the condition of the timer coil is driven.
If you use any of the T200–T250 in the program, the contact will act when the timer goes to the time. If the condition of driving the timer coil is true, the contact is kept, even if the condition of the driver timer coil is false, the contact is still kept, you need to reset the RST instruction, or MOV K0 T2XX. Reposition.